Flame control equipment to control and monitor gas burners, for continuous operation, ionization control, possible single electrode operation, possible multi-flame control, EC tested and certified.

IFD 450: Lockout due to failure following flame extinction
IFD 454: Retry after flame goes out,
Startup safety time:
3, 5 or 10 s,
Safety time for V2 operation: 1 s,
Safety time for V1 operation: 1 s,
Mains voltage: 220/240 V AC, for networks with or without earthing.